Radiator problem

K

kitzer

Guest
Hi Guys,
Hoping someone out there can help me, Got a new central heating system installed and today because of the cold weather decided to turn the heating on (Gas fired) all the radiators warmed up really well except the one in the sitting room which is only luke warm as opposed to the others, I bled the radiator in question and no air came out only water. I checked the inlet valve was turned fully on which it was fiddled with the other end and found that the valve was fully open what could be the problem? all comments welcome as it's the most important radiator in the house!

Kitzer
 
Turn off the other radiators (on one side only) when sitting room rad gets hot turn them back on.

If that doesn't work and you have thermostatic rad valves, this may be stuck. Besure that both valves are fully open.
 
Turn off the other radiators (on one side only) when sitting room rad gets hot turn them back on.

If that doesn't work and you have thermostatic rad valves, this may be stuck. Besure that both valves are fully open.

Kinda have the same problem meself.. Why would you only turn off the other rads on one side? will try it myself but just interested in the reasoning behind it..
 
Kinda have the same problem meself.. Why would you only turn off the other rads on one side? will try it myself but just interested in the reasoning behind it..



Because the rad heats by hot water circulation, you only need to shut down one side to break circulation and prevent flow.
 
Davy,

i have the same problem but i dont have thermostatic rad valves on my rads. there is one rad in the kitchen and one rad in the living room that just wont heat up. on the opposite side of the walls to these rads are other rads that are heating up just fine. i switched off all the rads last night then switched on the heating and went to the 2 rads that wont heat up and let a little water out to see if this would help. but nothing still happened. i will try again this evening and see if it works but can you think of anything else? i have let all the air out of the system as i have an air vent in the hot press and after letting that go no air came out????
thanks,

burger
 
Davy,

i have the same problem but i dont have thermostatic rad valves on my rads. there is one rad in the kitchen and one rad in the living room that just wont heat up. on the opposite side of the walls to these rads are other rads that are heating up just fine. i switched off all the rads last night then switched on the heating and went to the 2 rads that wont heat up and let a little water out to see if this would help. but nothing still happened. i will try again this evening and see if it works but can you think of anything else? i have let all the air out of the system as i have an air vent in the hot press and after letting that go no air came out????
thanks,

burger

As per above, it could be a CH balancing issue, ie that rad is being starved of hot water. Try http://www.diyfaq.org.uk/contents.html for methods to balance the system. It help such a rad in my house.

S.
 
Davy,

i have the same problem but i dont have thermostatic rad valves on my rads. there is one rad in the kitchen and one rad in the living room that just wont heat up. on the opposite side of the walls to these rads are other rads that are heating up just fine. i switched off all the rads last night then switched on the heating and went to the 2 rads that wont heat up and let a little water out to see if this would help. but nothing still happened. i will try again this evening and see if it works but can you think of anything else? i have let all the air out of the system as i have an air vent in the hot press and after letting that go no air came out????
thanks,

burger

Have they ever heated? and do they heat at all?

Are you 100% sure that both valves, either side of radiator are fully open?
 
Hi Davy,

i went home last night and shut off all the valves on the rads that were working. then i opend the valves on one of the rads that was not working. (opened both sides) then flicked on the heat and left it there for half an hour, and nothing. then opened the valves on the other rad that was not working (so that 2 rads should now heat up) and nothing. Nothing at all. i opened the vent at the top of the rad for about 30 seconds each to get some water flow going and still nothing. because the rads that are not working are connected to rads that are working i then opened the valves a little bit on the rads that were working (they are on the opposite side of the wall) to see if this could introduce some heat but nothing. the rads on the opposite side of the wall heated up alright but the other rads stayed cold. i have taken all the air out of the system through the air vent in the hot press, through the vent located in the boiler itself and also opened the vent at a rad at high level and still nothing!!!! the rads have worked before and got nice and hot and we were able to sit inside the living room nice and toasty. but now the blankets are out whilst in the living room to keep warm. (it doesnt help that we have no curtains or fire). so any other suggestions welcome. just to note that the connections to the rads that dont work dont even get hot before the valve.

from a very cold burger.
 
Thats very strange. Can you see where the rads connect to the other rads that are hot?

The line that feeds those two rads may be blocked. Time for a pro I think.
 
Hi,

Do you have thermostatic rad valves? If the answer is yes then the pin in the valve could be stuck.... that's what it sounds like to me. You could open the valve fully by turning all the way but the pin might be stuck down therefore keeping rad closed. Screw off top of thermostatic valve with your hand and you should see a pin. Check that this is moving up and down freely i.e. opening/closing the flow of hot water. They get stuck sometimes. If it is stuck just pull the pin up with a pliers which will open the flow of water into the rad and solve your problem. Mine stick from time to time especially after a period of non use.

Good Luck
Maddad
 
Hi DavyJones,

Oh you're so clever!!
This is a forum to offer advice and assistance to others.
I'm replying to the OP....."all comments welcome"
 
Hi DavyJones,

Oh you're so clever!!
This is a forum to offer advice and assistance to others.
I'm replying to the OP....."all comments welcome"


Did you take it personally?

I was pointing out that this reason was already discounted. Best to read entire thread .


oh and thanks for the clever, compliment.
 
As i jumped into this thread at the start, i'm gonna tell ya what i just did.

I closed off the 2 valves and unscrewed the nut connecting the rad to the valve and put a basin underneath. i opened the bleed screw and out came the water into a basin (leaving the bleed valve open releases any air lock in the rad).. When the rad was completely drained, i did the same on the other end of the rad..

Then, i locked up both nuts and opened up the valves again.. With the bleed screw still open, the rad filled back up again, and im now sitting in a sitting room thats toasty!! success!! Try it, it could be as simple as that!
 
hi folks. I have come across this issue many times in my area. The problem is that these rads are usually drop fed (the pipes come from the ceiling down rather than up from the floor) and on either the flow or return pipe where it's bend meets the ceiling is airlocked. Drain and remove rad. Turn on heating. Over pressurize system then open each rad valve in turn until you get hot water at either side (the one that splurtters is where the airlock was let it run until u get a constant flow) when finished you will need to top your system water back up and add some inhibitor
 
Another cold rad here :(

A bit of history, the rad is in a converted garage. Rad was in garage before it was converted but was obviously turned off from time house was built to conversion (approx 2.5 years).

As part of the conversion I moved the rad up a few inches as I raised the floor. Obviously this necessitated removing rad, all went well and the rad was piping hot.
Not long after the rad no longer gets piping hot, turning off all other rads improves it but only just. Unlike many problems with cold rads this one is in fact the second closest to the boiler...

Having read previous posts I suspect that there may be a blockage in pipes either side of rad or in rad itself. I guess having rad turned off for so long could have contributed to build up of sludge/sediment n pipes in vicinity of rad?

I am planning to tackle this again. Am thinking of:
- removing rad, and running water through it
Then, with rad still disconnected :
- connecting hose to return pipe where rad is situtated and then connect mains water to say return pipe of another rad.
- repeat with hose connected to "feed" pipe of troublesome rad
I would hope that this would flush out any sludge in either feed or return pipes of rad.

Would be grateful if someone could offer advice if this is a good strategy and/or advise on an alternative?

Also, with regard to inhibitors. Do you simply add this to feed tank in attic before refilling the system? I presume I can buy that at some place like Heat Merchants?

thanks,
cybermate
 
Hi,

Do you have thermostatic rad valves? If the answer is yes then the pin in the valve could be stuck.... that's what it sounds like to me. You could open the valve fully by turning all the way but the pin might be stuck down therefore keeping rad closed. Screw off top of thermostatic valve with your hand and you should see a pin. Check that this is moving up and down freely i.e. opening/closing the flow of hot water. They get stuck sometimes. If it is stuck just pull the pin up with a pliers which will open the flow of water into the rad and solve your problem. Mine stick from time to time especially after a period of non use.

Good Luck
Maddad
Same problem here. Pulled pin up but no go. Rad has been off for years. Bled it and that is fine. Any idea anyone?
 
Back
Top